Installation Instructions BGD258
Issue Date November 9, 2012
© 2012 BASO Gas Products
1
Part No. BASO-INS-BGD258, Rev. F www.baso.com
BGD258 Series BASOTROL®
CE Approved Class A Gas Valve
Installation
IMPORTANT: These instructions are intended as a
guide for qualified personnel installing or servicing
BASO Gas Products. Carefully follow all instructions
in this bulletin and all instructions on the appliance.
Limit repairs, adjustments, and servicing to the
operations listed in this bulletin or on the appliance.
!
WARNING: Risk of Fire or Explosion.
The system must meet all applicable local, national,
and regional regulations. Improper installation may
cause gas leaks, explosions, property damage, and
injuries.
!
WARNING: Risk of Fire or Explosion.
To prevent leakage of upstream gas, shut off the gas
supply at the main manual shutoff valve before
installing or servicing the BGD258 valve. Failure to
shut off the gas supply can result in the release of
gas during installation or servicing, which can lead to
an explosion or fire, and may result in severe
personal injury or death.
Mounting
!
CAUTION: Risk of Equipment Damage.
To prevent damage to the valve when mounting to
pipework, do not use a wrench on any surface other
than the casting flats provided at the inlet and outlet
ends of the valve body.
To install the BGD258 valve:
1. Ensure that the specified maximum ambient
(surface) temperature is not exceeded (see the
Technical Data section).
2. Ensure that the power supply voltage is
compatible with the required control valve voltage.
3. Shut off the gas at the main manual shutoff valve.
4. When installing the valve on the manifold, ensure
that the gas flows through the valve body in the
direction indicated by the arrow on the valve body.
If the valve is installed with the gas flow in the
opposite direction of the arrow, leakage can occur.
5. Mount the valve to the pipework. The BGD258
valve may be mounted on a horizontal manifold
with the solenoid coils pointed up (vertical) or in
any position not exceeding 90° from the vertical.
The valve also may be mounted on a vertical
manifold in any position around its axis (see
Figure 1). Do not install the solenoid coil upside
down. Install vertically wherever possible.
90° Maximum
from Vertical
90° Maximum
from Vertical
Limited Horizontal and Vertical
Vertical mounting may
be 36 around its axis
with the gas flow either
up or down, but always in
the direction of the arrow.
No
Regulator
Figure 1: BGD258 Valve Mounting Positions
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - BGD258 Series BASOTROL®

Installation Instructions BGD258 Issue Date November 9, 2012 © 2012 BASO Gas Products 1 Part No. BASO-INS-BGD258, Rev. F www.baso.com B

Page 2 - Tap Connection

2 BASOTROL CE Approved Gas Valve Installation Instructions 6. Use an approved pipe joint sealing compound on the male threads before assembly. Re

Page 3 - Repairs and Replacement

BASOTROL CE Approved Gas Valve Installation Instructions 3 Wiring ! WARNING: Risk of Electrical Shock. Disconnect the power supply before making

Page 4

4 BASOTROL CE Approved Gas Valve Installation Instructions LNLNNon-Polarity SensitiveLine and NeutralConnectionsNon-Polarity SensitiveLine and Neu

Page 5 - Technical Specifications

BASOTROL CE Approved Gas Valve Installation Instructions 5 Technical Specifications Product BGD258 Series BASOTROL CE Approved Class A Gas Valve

Page 6

6 BASOTROL CE Approved Gas Valve Installation Instructions Technical Specifications (continued) Agency Listings CSA (AGA/CGA) Certificate Number